B) Duct Sensor - For single point monitoring. It is available with various probe lengths and enclosures to fit any application.


D) Duct Average Sensor - Incorporates numerous sensors inside a copper tube. It acts as a single sensor, averaging any temperature change across the sensors.


F) OSA Sensor - Comes in a weatherproof enclosure. It incorporates a sun/wind shield to protect the sensor and provide accurate readings.
 




The TE Series Temperature sensors offer a choice of precision platinum RTD's, IC, or NTC thermistor sensors which can be interfaced with a computerized monitoring or control system.

The sensors are available in different housings, with various configurations and options for duct, immersion, duct averaging, remote strap-on and outside air applications.

The single point sensors are encapsulated in a 6.35 mm (0.25") OD 304 stainless steel probe.  All probes are constructed to provide good heat transfer and fast response.  The averaging sensors are available in both plenum rated cable or with a copper probe.




C) Immersion Sensor - Comes in two configurations. It has either spring loaded or non-spring loaded probes and has a 1/2" NPT fitting to be mounted into a thermowell. It is available in various lengths and enclosures styles.

E) Strap-on Sensor - Is a stainless steel probe and is used in remote applications where an immersion sensor can not be installed.


FD) Flex-Duct Sensor -Is made of flexible plenum rated cable which incorporates numerous sensors along the assembly. It acts as a single sensor averaging any temperature change across the sensors.





The TE500 transmitter option is standard with the 1000 ohm platinum sensor and provides either 4-20mA, 0-5 VDC or 0-10 VDC output over a selected range. It is powered by either 24 VAC or VDC. A 100 ohm platinum sensor transmitter is optional.


Transmitter General Specifications:
Supply Voltage:
Output:
Accuracy:
Operating Temp.:
OSA Operating Temp.:

24 VDC/VAC
4-20mA, 0-5 VDC or 0-10 VDC
¡À0.1% of span
0¡ãC-70¡ãC (32¡ãF-158¡ãF)
-40¡ãC-85¡ãC (-40¡ãF-185¡ãF)



    NOTE:
    Standard probe assemblies are rated at -40¡ãC-105¡ãC (-40¡ãF-221¡ãF). For higher or lower temperature applications, please contact Greystone.